Circuit Breaker

YJB1Z-63 Small DC Circuit Breaker

YJB1Z-63 series DC miniature circuit breaker (hereinafter referred to as circuit breaker) is suitable for circuits with rated current of 63A and below, and DC rated voltage of 250V and 440V. Used for overload and short circuit protection of facilities and electrical equipment in DC distribution systems, it can be widely used in…

  • YJB1Z-63 Small DC Circuit Breaker
  • YJB1Z-63 Small DC Circuit Breaker
  • YJB1Z-63 Small DC Circuit Breaker
  • YJB1Z-63 Small DC Circuit Breaker

  • YJB1Z-63 Small DC Circuit Breaker
  • YJB1Z-63 Small DC Circuit Breaker
  • YJB1Z-63 Small DC Circuit Breaker
  • YJB1Z-63 Small DC Circuit Breaker

YJB1Z-63 Small DC Circuit Breaker
YJB1Z-63 series DC miniature circuit breaker (hereinafter referred to as circuit breaker) is suitable for circuits with rated current of 63A and below, and DC rated voltage of 250V and 440V. Used for overload and short circuit protection of facilities and electrical equipment in DC distribution systems, it can be widely used in industries such as power, postal and telecommunications, transportation, and industrial and mining enterprises.
This product complies with the requirements of GB10963.2 and IEC60898-2 standards.

Scope of use

YJB1Z-63 series DC miniature circuit breaker (hereinafter referred to as circuit breaker) is suitable for circuits with rated current of 63A and below, and DC rated voltage of 250V and 440V. Used for overload and short circuit protection of facilities and electrical equipment in DC distribution systems, it can be widely used in industries such as power, postal and telecommunications, transportation, and industrial and mining enterprises.

This product complies with the requirements of GB10963.2 and IEC60898-2 standards.

Model meaning and classification

YJB1Z-63 Small DC Circuit Breaker

Product Features

The YJB1Z-63 DC circuit breaker consists of a housing, operating mechanism, thermal release, electromagnetic release contact system, arc extinguishing system, etc. It has overload and short circuit protection functions. The unique design of the structure and strong permanent magnet arc extinguishing system make the product have a short circuit capacity of 10KA and a mechanical life of more than 20000 times. The product has a beautiful appearance and the installation guide rail is made of TH35-7.5 standard steel. It has the following characteristics: the handle is designed above the front end face for safe and comfortable operation, and attention must be paid to the polarity of “+” and “-” when wiring. The power supply enters and exits, which conforms to the characteristics of power supply entering and exiting. It is easy to install and saves wires.

Technical Parameter

Shell level rating
Constant current 1mm
(A)
number of poles Width/Position
(18mm
Multiple)
rated voltage
(V)
Rated current In (A) Rated ultimate short-circuit capacity Instantly detached
Buckle type
Breaking current
Icu(A)
time constant
T(ms)
sixty-three one one DC125V/220V 1. 2, 3, 4, 5
6. 10, 15, 16
20. 25, 32
40, 50, 63A
ten thousand
six thousand
ten B、C
two two DC250V/440V

Note: 1P DC220V, 2P DC440V need to be customized

Standard Time – Current

test Instantly detached
Buckle type
DC test
Test current
Initial state Tripping or non tripping time limit Expected results notes
a B、C| 1.13In cold state t≥1h(ln≤63A) Do not release
b B、C 1.45In Immediately after
Experiment A
t<1h(ln≤63A) trip Current at 5 seconds
Internally stable increase
C B、C 2.55In cold state 1s<t<60s(In≤32A)
1s<t<120s(In>32A)
trip
d B、C 4In cold state 0.1s≤t≤45s(In≤32A)
0.1s≤t≤90s(In>32A)
trip Closing assistance
switch on
power supply
7In 0.1s≤t≤15s(In≤32A)
0.1s≤t≤30s(In>32A)
e B、C 7In cold state t<0.1s trip
15In

Wiring diagram

YJB1Z-63 Small DC Circuit Breaker

Installation and overall dimensions

YJB1Z-63 Small DC Circuit Breaker

WeChat
+86 135 8775 6198
Phone
+86 135 8775 6198
Email