Scope applicationThe multifunctional overvoltage, undervoltage, and overcurrent intelligent protector is a comprehensive intelligent protector that integrates overvoltage protection, undervoltage protection, and overcurrent protection. When any line experiences overvoltage, undervoltage, or overcurrent faults, this product can instantly cut off the power supply to avoid unnecessary damage to electrical equipment.When the line returns to normal, the protector…

  • YJAR automatic closing overvoltage protector for lightning protection
  • YJAR automatic closing overvoltage protector for lightning protection
  • YJAR automatic closing overvoltage protector for lightning protection

  • YJAR automatic closing overvoltage protector for lightning protection
  • YJAR automatic closing overvoltage protector for lightning protection
  • YJAR automatic closing overvoltage protector for lightning protection

YJAR automatic closing overvoltage protector for lightning protection
Automatic reclosing leakage protector is a new generation of high-tech intelligent safety electrical product that breaks through traditional safety electrical protection methods and combines mechanical automation with modern electronic control technology. This product achieves online detection function and overload (overcurrent), short circuit, overvoltage, undervoltage, and leakage protection function through microcomputer control technology. The product integrates switch and protection, realizing comprehensive protection for digital safe electricity use, and also has anti lightning surge function. Once an electrical fault is detec···

Scope application

Automatic reclosing leakage protector is a new generation of high-tech intelligent safety electrical product that breaks through traditional safety electrical protection methods and combines mechanical automation with modern electronic control technology. This product achieves online detection function and overload (overcurrent), short circuit, overvoltage, undervoltage, and leakage protection function through microcomputer control technology. The product integrates switch and protection, realizing comprehensive protection for digital safe electricity use, and also has anti lightning surge function. Once an electrical fault is detected during use, it is immediately protected and tripped. After the fault is eliminated, it automatically recloses without human intervention, fundamentally solving the problem of power interruption due to electrical fault tripping and inability to automatically reclose.

This product is suitable for industries such as communication, transportation, industrial and mining enterprises, intelligent residential areas, petrochemicals, etc., and has a large number of successful application cases in wireless base station equipment, broadband switches, monitoring equipment, meteorological monitoring equipment, etc.

Model Meaning

YJAR automatic closing overvoltage protector for lightning protection

Product Features

Intelligent design, automatic protection and reclosing based on electricity usage

Multi gear selection of rated current for more flexible use

Powerful functionality, online comprehensive detection of various electrical faults

Accurate digital diagnosis and warning, faster and more accurate alarm and protection

Normal working conditions

1. Surrounding air temperature

a. The upper limit value shall not exceed+40 ℃.

b. The lower limit value shall not be lower than -4 ℃ ℃.

c. The average value within 24 hours shall not exceed+30 ℃,

d. Extreme operating temperature -40 ℃~+75 ℃

2. The altitude of the installation location shall not exceed 2000 meters.

3. Atmospheric conditions

a. When the ambient air temperature is+35 ℃, the relative humidity of the air does not exceed 50%, and there can be higher relative humidity at lower temperatures.

b. When the monthly average lowest temperature of the wettest month is 20 ℃, the monthly average relative humidity is 90%.

c. We have taken into account the condensation that may occur on the surface of the product due to temperature changes. 4. Pollution level

The pollution level used for the protector is level 2,

5. Installation category

The installation category is worker or Class III.

Technical Parameter

5.1 Rated working voltage: AC230V。

5.2 Rated current In: 1A-63A/1A-100A adjustable.

5.3 Lifespan: Electrical lifespan of 20000 on-off cycles.

5.4 Local power consumption:< 3W.

5.5 Operating voltage range: AC120V-320V。

5.6 Maximum rated output current: In63A/100A.

5.7 Leakage protection setting range: 10-90mA, action time ≤ 0.1S

5.8 Under voltage protection setting range: AC140-190V, Action time 2-5 seconds

5.9 Overvoltage protection setting range: AC240-300V, Action time 2-5 seconds.

5.10 Overcurrent protection setting range: 1A-63A; 63A-100A, action time 2-5S5.11 Short circuit protection current:> 3ln, action time ≤ 0.1S.

5.12 Lightning protection: Add a 1.2/50us (8/20us) combined wave between L-N, with no misoperation at 2KV and no damage at 8KV.

The relationship between the automatic reclosing frequency and time of the 5.14 protector is shown in the following table:

Automatic reclosing frequency Automatic reclosing delay time
00C times At this time, if the product has no automatic reclosing function and disconnects due to a fault, manual reclosing is required.
001 times 30 seconds
002 times 5 minutes
003 times 10 minutes
004 times 30 Minutes
005 times 60 Minutes

Real time display of voltage, current, and residual current with an error of ≤ 5%.

5.15 The maximum number of fault information saved is 999.

5.16 Installation: Installed on a 35×7.5mm standard guide rail.

PRODUCT FUNCTION

a. Pre closing detection: The product checks the circuit before closing, and cannot close when any faults such as overvoltage, undervoltage, electricity, or overcurrent exist.

b. Overvoltage protection: Automatically disconnects when the input voltage exceeds the set value

c. Undervoltage protection: It automatically disconnects when the input voltage is less than the set value or when there is a power outage.

d. Overcurrent protection: When the current is greater than or equal to 1.15 times the rated current, the protector will automatically disconnect for 3 seconds

Open it.

e. Short circuit protection: When the current exceeds 3 times the rated current, the protector automatically disconnects within 0.1 seconds

f. Residual current protection: When the leakage current exceeds the set value or is touched by a person, the protector will automatically disconnect within 0.1 seconds

Open it.

9. Neutral wire disconnection protection: When the neutral wire is disconnected or loose, and the voltage imbalance reaches a certain value, the protector will automatically disconnect

h. Power outage protection: The protector automatically disconnects when there is a power outage, and automatically closes when the incoming call detection is normal.

i. Automatic closing: Automatically disconnect when a fault occurs; Self closing after troubleshooting.

i. Automatic saving of information: Various information about automatic disconnection, including disconnection frequency, time, fault type, etc., provides a basis for fault analysis.

k. Sound and light fault alarm: When the fault is disconnected, the corresponding fault indicator light will light up and an audible alarm will sound.

Product size

YJAR automatic closing overvoltage protector for lightning protection

WeChat
+86 135 8775 6198
Phone
+86 135 8775 6198
Email