Surge Protection Device

YJ1-C40 surge protector

Product IntroductionThis series of surge protectors is suitable for TT, IT, TN-S, N-C-S and other power supply systems with AC 50Hz, 380V and below, and can be used as equipotential connections at the interface of LPZ1, LP22 and LP23 zones. Its design basis complies with IEC61643-1, GB18802.1, The shell is designed to be installed on…

  • YJ1-C40 surge protector
  • YJ1-C40 surge protector
  • YJ1-C40 surge protector
  • YJ1-C40 surge protector
  • YJ1-C40 surge protector
  • YJ1-C40 surge protector

  • YJ1-C40 surge protector
  • YJ1-C40 surge protector
  • YJ1-C40 surge protector
  • YJ1-C40 surge protector
  • YJ1-C40 surge protector
  • YJ1-C40 surge protector

YJ1-C40 surge protector
This series of surge protectors is suitable for TT, IT, TN-S, N-C-S and other power supply systems with AC 50Hz, 380V and below, and can be used as equipotential connections at the interface of LPZ1, LP22 and LP23 zones. Its design basis complies with IEC61643-1, GB18802.1, The shell is designed to be installed on a 35mm electrical rail, and the product has a built-in failure release device. When the surge protector fails due to overcurrent, overheating, or breakdown, the failure release device can automatically disconnect it from the power grid, and the visual alarm indicator window changes from green (normal) to red (fault).

Product Introduction

This series of surge protectors is suitable for TT, IT, TN-S, N-C-S and other power supply systems with AC 50Hz, 380V and below, and can be used as equipotential connections at the interface of LPZ1, LP22 and LP23 zones. Its design basis complies with IEC61643-1, GB18802.1, The shell is designed to be installed on a 35mm electrical rail, and the product has a built-in failure release device. When the surge protector fails due to overcurrent, overheating, or breakdown, the failure release device can automatically disconnect it from the power grid, and the visual alarm indicator window changes from green (normal) to red (fault).

application

The YJ1 series module is used for equipotential connection during lightning strikes and is installed at the junction of LPZOB zone, LPZ1 zone, and LPZ2 zone. It is usually installed in floor distribution boxes, computer centers, telecommunications rooms, elevator control rooms, frequency conversion equipment control rooms, hospital operating rooms, monitoring rooms, and distribution boxes in places where electronic medical equipment is installed. SPD should be installed in residential distribution boxes for dispersed small villas.

Product design and ordering instructions: Users should clearly indicate the product model and quantity when designing and ordering products.

Product Features

a、 The integrated design module design is safer and more reliable;

b、 Can withstand up to 40kA (8/21 μ s) lightning current surge;

c、 Action response time less than 25 nanoseconds;

d、 The color of the visual window indicates the working status of the protection, green (normal) and red (fault).

e、 High energy surge protection

f、 Remote signaling alarm interface

g、 Failure detection indication

h、 Standard modular installation

i、 Reaction speed: nanosecond level

j、 Built in instantaneous overcurrent circuit breaker device

k、 The maximum discharge current of a single module is 40kA (8/21 μ S)

l、 Built in overheat circuit breaker device

Normal working conditions

1. The ambient air temperature ranges from -40 ℃ to+70 ℃, with an average value not exceeding+35 ℃ within 24 hours.

2. The altitude shall not exceed 2000m.

3. The relative humidity of the air at the installation site under atmospheric conditions shall not exceed 50% at a maximum temperature of+40 ℃; Higher relative humidity is allowed at lower temperatures, with the average lowest temperature of the wettest month not exceeding+25 ℃ and the average maximum relative humidity of that month not exceeding 90%. And taking into account the condensation that occurs on the surface of the product due to temperature changes.

4. Pollution level: Level 2.

5. Installation category: Category II

6. Installation method: Adopting international standard guide rails.

Main parameters and technical performance

model YJ1-C40
specifications 1P/2P/3P/4P
SPD category Pressure limiting type
Experimental category Class II experiment
Rated voltage Un 220V AC 50Hz
Maximum continuous operating voltage Uc (L-N) 385V AC 50Hz
Maximum continuous operating voltage Uc (N-PE) 255V AC 50Hz
Nominal discharge current Ln (L-N) (8/20 μ s) 20kA
Maximum discharge current 1max (L-N) (8/20 μ s) 40kA
Voltage protection level Up (L-N) (8/20 μ s) 1.8kV
Voltage protection level Up (N-PE) (8/20 μ s) 1.8kV
Recommended series receiving current protection device 32A/10kA
Response time tA (L-N) ≤25ns
Failure indication Green: Normal Red: Failure
Installation of wire cross-sectional area 4-25mm²
Installation method 35mm standard guide rail
work environment -40℃~+70℃
Housing material Plastic meets UL94 V-0 standards
protection grade IP20
Remote signaling alarm Normally open and normally closed contact terminals (optional)
Remote signaling interface wiring capability Maximum 1.5mm ²

Wiring diagram

YJ1-C40 surge protector

Product size parameters

YJ1-C40 surge protector